Huawei ETP48200-C5C4-001 is an embedded telecom power system that supplies power to –48 V DC communications equipment with a maximum current of 200 A

Description

Overview

ETP48200-C5C4-001 is an embedded telecom power system that supplies power to –48 V DC communications equipment with a maximum current of 200 A.

 

ETP48200-C5C4-001 Appearance

ETP48200 C5C4 001 pic

 

(1) PDU

(2) Ground screw

(3) Space for rectifiers

(4) SMU02B

(5) UIM02C

 

 

System Configurations

Item ETP48200-C5C4-001

Subrack

  • 3 U power distribution space
  • 1 U monitoring unit
  • 1 U rectifier space

PDU

  • AC power distribution: AC input circuit breaker, AC output circuit breaker
  • DC power distribution: battery low voltage disconnection (BLVD) route, load low voltage disconnection (LLVD) route, and battery route

Rectifier

A maximum of four R4850N2s or R4850G2s

Monitoring module

SMU02B

User interface module (UIM)

UIM02C

Surge protective device (SPD)

AC surge protection: nominal lightning strike discharge current of 30 kA (8/20 µs), maximum lightning strike discharge current of 60 kA (8/20 µs)

DC surge protection: 10 kA (8/20 µs) in differential mode, 20 kA (8/20 µs) in common mode

Item ETP48200-C5C4-001

AC input

Input system

127/220 V AC three-phase three-wire, compatible with 220/380 V AC three-phase four-wire

Input frequency

45–65 Hz (rated frequency: 50 Hz or 60 Hz)

Power factor (PF)

≥ 0.99 (rated input, with 100% loads)

DC output

Output voltage range

–42 V DC to –58 V DC

Default output voltage

–53.5 V DC

Max. output power

8700 W

Regulated voltage precision

≤ ±1% (The output voltage is within 53.5 V DC ±0.1 V DC at 50% loads.)

Peak-to-peak noise voltage

≤ 200 mV (rated input voltage and load)

Psophometrically weighted noise

≤ 2 mV (300–3400 Hz, input power ≤ 264 V AC)

Current imbalance

≤ ±5% (50%–100% load)

AC input protection

AC input overvoltage protection threshold

≥ 300 V AC

AC input overvoltage recovery threshold

290–300 V AC

AC input undervoltage protection threshold

≤ 85 V AC

AC input undervoltage recovery threshold

85–90 V AC

DC output protection

DC output overvoltage protection threshold

–58.5 V DC to –-60.5 V DC

  • If overvoltage occurs inside a rectifier, the rectifier locks out.
  • If the external voltage is greater than –63 V DC for more than 500 ms, the rectifier locks out.

AC surge protection

Nominal lightning strike discharge current: 30 kA (8/20 µs); maximum lightning strike discharge current: 60 kA (8/20 µs)

DC surge protection

10 kA (8/20 μs) in differential mode; 20 kA (8/20 μs) in common mode

Safety compliance

Compliant with IEC/EN60950-1 and GB4943, CE certification

Mean time between failures (MTBF)

200,000 hours (at 25ºC)

Dimensions (H x W x D)

219.5 mm x 482.6 mm x 330 mm

Weight

≤ 20 kg (excluding rectifiers)

Protection level

IP20

Installation mode

Installed in a 19-inch rack

Cabling

Routed in and out from the top

Maintenance mode

Maintained from the front

Cooling

Natural cooling

Additional information