Huawei ETP48200-C5C9 is an embedded telecom power system that supplies power to –48 V DC communications equipment with a maximum current of 200 A

Description

Overview

ETP48200-C5C9 is an embedded telecom power system that supplies power to –48 V DC communications equipment with a maximum current of 200 A.

 

ETP48200-C5C9 Appearance

ETP48200 C5C9 pic

 

(1) LLVD2 wiring terminals

(2) Ground screw

(3) AC input terminals

(4) LLVD1 wiring terminals

(5) SMU02B

(6) RTN+ busbar

(7) Battery switch (behind the cover)

(8) Battery wiring terminals

(9) BLVD wiring terminals

(10) UIM02C

(11) Space for rectifiers

 

 

System Configurations

Item ETP48200-C5C9

Application environment

Indoor Class B

Subrack

  • 3 U power distribution space
  • 1 U SMU space
  • 1 U rectifier and SSU space

Power distribution unit (PDU)

  • Input power distribution: AC input terminals
  • Output power distribution: battery low voltage disconnection (BLVD) route, load low voltage disconnection 1 (LLVD1) route, load low voltage disconnection 2 (LLVD2) route, and battery route

Rectifier

A maximum of four R4850G2s

SMU

SMU02B

User interface module (UIM)

UIM02C

Surge protective device (SPD)

DC surge protection. Differential mode: 10 kA (8/20 µs); common mode: 20 kA (8/20 µs)

Item ETP48200-C5C9

AC input

Input system

220 V AC input for rectifiers

Input frequency

45–66 Hz (rated frequency: 50 Hz or 60 Hz)

Power factor (PF)

≥ 0.99 (rated input and load)

DC output

Output voltage range

–42 V DC to –58 V DC

Default output voltage

–53.5 V DC

Maximum output power

12,000 W

Regulated voltage precision

≤ ±1% (output voltage of within 53.5 V ±0.1 V at 50% load)

Peak-to-peak noise voltage

≤ 200 mV (rated input voltage and load)

Psophometrically weighted noise

≤ 2 mV (300–3400 Hz; input power ≤ 264 V AC)

Current sharing imbalance

≤ ±5% (50%–100% load)

AC input protection

AC input overvoltage protection threshold

≥ 300 V AC

AC input overvoltage recovery threshold

290–300 V AC

AC input undervoltage protection threshold

≤ 80 V AC

AC input undervoltage recovery threshold

80–90 V AC

DC output protection

DC output overvoltage protection threshold

–58.5 V DC to –60.5 V DC

  • If overvoltage occurs due to an internal fault, the rectifier locks out.
  • If the external voltage is greater than –63 V DC for more than 500 ms, the rectifier locks out.

DC surge protection

Differential mode: 10 kA (8/20 μs); common mode: 20 kA (8/20 μs)

Safety

IEC/EN60950-1/GB 4943 and CE certification

Mean time between failures (MTBF)

200,000 hours (at 25°C)