ETP11005-C1A1

0 Reviews Write a review
SKU2026041
AvailabilityIn Stock
WarrantyUp to 36 months i
×
Warranty Policy
We provide a comprehensive warranty policy.
Refer to the table for more details.

The Huawei ETP11005-C1A1 can convert –48 V DC power into 100 V AC/110 V AC/115 V AC/120 V AC/127 V AC power to AC equipment.

Description

Overview

Working with Huawei monitoring module, the ETP11005-C1A1 can convert –48 V DC power into 100 V AC/110 V AC/115 V AC/120 V AC/127 V AC power to AC equipment.

 

ETP11005-C1A1 Features:
  • Reliable: N+1 backup of AC modules
  • Intelligent management: supports CAN remote management.
  • Easy maintenance: The inverter module is hot-swappable.

Environmental specifications

Item ETP11005-C1A1

Operating temperature

–20°C to +65°C

Transportation temperature

–40°C to +75°C

Storage temperature

–40°C to +75°C

Relative humidity

5% RH–95% RH

Altitude

0 m–5000 m

When the altitude ranges from 2000 m to 5000 m, high temperature derating applies and the operating temperature decreases by 1°C for each additional 200 m.

Noise level

≤ 60 dBa (acoustic pressure)

Operating environment

Class B environment

Other requirements

  • There should be no conductive dust, corrosive gas, or explosion hazard.
  • Dust, corrosive substances, pests, molds, and other indicators should be controlled in accordance with Class 4.1 requirements in ETSI EN 300 019-1-4 (V2.2.1).

Inverter module (I10002G1) specifications

Item ETP11005-C1A1

Input

Operating voltage range

42–58 V DC (rated voltage: 53.5 V DC)

Input current range

25–40 A

Output

Load power factor

≥ 0.8

Output voltage range

100 V AC by default. The output voltage can be set to 100 V AC, 110 V AC, 115 V AC, 120 V AC, or 127 V AC on the monitoring module.

Output frequency range

50 Hz by default. The output frequency can be set to 50 Hz or 60 Hz.

Output regulated voltage precision

≤ ±1%

Output regulated frequency precision

≤ ±0.2%

DC component in output voltage

≤ ±200 mV (rated input, rated output)

Total harmonic distortion of output voltage (THDv)

≤ ±3% (rated output, resistive load)

≤ ±6% (rated output, non-resistive load)

Output current peak factor

≥ 3:1 (The current peak factor is greater than or equal to 3 when the rated input and output capacity is 1000 VA.)

Output overload capability (resistive load)

105% ≤ Load power ≤ 125%; T > 10 min

125% < Load power ≤ 150%; T > 10s

Load power > 150%; T ≤ 1s

Dynamic voltage transient recovery time

≤ 60 ms

Dynamic voltage transient

≤ ±5%

Delayed shutdown time upon fan faults

15s±1s

Output discharge time

≤ 1s

Standby power

≤ 5 W

Protection specifications

Input overvoltage protection range

59–61 V DC

Input overvoltage recovery range

57–59 V DC

Input undervoltage protection range

40–42 V DC

Input undervoltage recovery range

45–47 V DC (input undervoltage recovery threshold: 3–5 V)

Input reverse connection protection

The module is not damaged if positive and negative terminals are reversely connected.

Overtemperature protection

Supported

Dimensions (H x W x D)

40.8 mm x 105 mm x 269 mm

Weight

<2 kg

IP rating

IP20

 Inverter specifications

Item

ETP11005-C1A1 (01076057)

ETP11005-C1A1 (01076057-001)

Input voltage range

43.2–58 V DC

43.2–58 V DC

Undervoltage protection threshold

Protection threshold: 41 V; recovery threshold: 46 V

Protection threshold: 41 V; recovery threshold: 46 V

Overvoltage protection threshold

Protection threshold: 60 V; recovery threshold: 58 V

Protection threshold: 60 V; recovery threshold: 58 V

Output voltage

110 V AC±3%

100 V AC±3%

Output frequency

60 Hz±1%

50 Hz±1%

Output power factor

0.8

0.8

Communications port

CAN

CAN

Peak efficiency

≥ 90%

≥ 90%

Certification

CE

CE/VCCI

Cooling mode

Free cooling

Free cooling

Cabling mode

Connected from the left and right

Connected from the left and right

IP rating

IP20

IP20

 

EMC specifications

Item

Specifications

Inverter (01076057)

Inverter (01076057-001)

Electromagnetic interference (EMI)

Conducted emission (CE)

EN55032, Class A

Radiated emission (RE)

EN55032, Class A

Electromagnetic susceptibility (EMS)

Electrostatic discharge (ESD)

EN61000-4-2

  • Enclosure: ±6 kV contact discharge, ±8 kV air discharge (criterion B)
  • Signal port: ±2 kV contact discharge (criterion R)

Electrical fast transient (EFT)

EN61000-4-4

  • Power port: ±2 kV/5 kHz (criterion B)
  • Signal port: ±1 kV/5 kHz (criterion B)

Radiated susceptibility (RS)

EN61000-4-3

10 V/m (criterion A)

Conducted susceptibility (CS)

EN61000-4-6

10 V (criterion A)

Surge susceptibility

EN61000-4-5

  • AC power port: ±6 kV in both horizontal and vertical directions (criterion B)
  • DC power port: ±2 kV in differential mode, ±4 kV in common mode (criterion B)
  • Northbound network port: 1 kV in differential mode, 2 kV in common mode (criterion B); southbound network port: 0.5 kV in differential mode, 1 kV in common mode (criterion B)
  • Dry contact: 1 kV in differential mode, 1 kV in common mode (criterion B)

Surge protection

AC power port: 30 kA in differential mode, 30 kA in common mode (8/20 μs) (criterion C)

AC power port: 20 kA in differential mode, 20 kA in common mode (8/20 μs) (criterion C)

Additional information

Brand

Huawei

Inverter module (I10002G1) specifications

Item ETP11005-C1A1

Input

Operating voltage range

42–58 V DC (rated voltage: 53.5 V DC)

Input current range

25–40 A

Output

Load power factor

≥ 0.8

Output voltage range

100 V AC by default. The output voltage can be set to 100 V AC, 110 V AC, 115 V AC, 120 V AC, or 127 V AC on the monitoring module.

Output frequency range

50 Hz by default. The output frequency can be set to 50 Hz or 60 Hz.

Output regulated voltage precision

≤ ±1%

Output regulated frequency precision

≤ ±0.2%

DC component in output voltage

≤ ±200 mV (rated input, rated output)

Total harmonic distortion of output voltage (THDv)

≤ ±3% (rated output, resistive load)

≤ ±6% (rated output, non-resistive load)

Output current peak factor

≥ 3:1 (The current peak factor is greater than or equal to 3 when the rated input and output capacity is 1000 VA.)

Output overload capability (resistive load)

105% ≤ Load power ≤ 125%; T > 10 min

125% < Load power ≤ 150%; T > 10s

Load power > 150%; T ≤ 1s

Dynamic voltage transient recovery time

≤ 60 ms

Dynamic voltage transient

≤ ±5%

Delayed shutdown time upon fan faults

15s±1s

Output discharge time

≤ 1s

Standby power

≤ 5 W

Protection specifications

Input overvoltage protection range

59–61 V DC

Input overvoltage recovery range

57–59 V DC

Input undervoltage protection range

40–42 V DC

Input undervoltage recovery range

45–47 V DC (input undervoltage recovery threshold: 3–5 V)

Input reverse connection protection

The module is not damaged if positive and negative terminals are reversely connected.

Overtemperature protection

Supported

Dimensions (H x W x D)

40.8 mm x 105 mm x 269 mm

Weight

<2 kg

IP rating

IP20

 Inverter specifications

Item

ETP11005-C1A1 (01076057)

ETP11005-C1A1 (01076057-001)

Input voltage range

43.2–58 V DC

43.2–58 V DC

Undervoltage protection threshold

Protection threshold: 41 V; recovery threshold: 46 V

Protection threshold: 41 V; recovery threshold: 46 V

Overvoltage protection threshold

Protection threshold: 60 V; recovery threshold: 58 V

Protection threshold: 60 V; recovery threshold: 58 V

Output voltage

110 V AC±3%

100 V AC±3%

Output frequency

60 Hz±1%

50 Hz±1%

Output power factor

0.8

0.8

Communications port

CAN

CAN

Peak efficiency

≥ 90%

≥ 90%

Certification

CE

CE/VCCI

Cooling mode

Free cooling

Free cooling

Cabling mode

Connected from the left and right

Connected from the left and right

IP rating

IP20

IP20

 

EMC specifications

Item

Specifications

Inverter (01076057)

Inverter (01076057-001)

Electromagnetic interference (EMI)

Conducted emission (CE)

EN55032, Class A

Radiated emission (RE)

EN55032, Class A

Electromagnetic susceptibility (EMS)

Electrostatic discharge (ESD)

EN61000-4-2

  • Enclosure: ±6 kV contact discharge, ±8 kV air discharge (criterion B)
  • Signal port: ±2 kV contact discharge (criterion R)

Electrical fast transient (EFT)

EN61000-4-4

  • Power port: ±2 kV/5 kHz (criterion B)
  • Signal port: ±1 kV/5 kHz (criterion B)

Radiated susceptibility (RS)

EN61000-4-3

10 V/m (criterion A)

Conducted susceptibility (CS)

EN61000-4-6

10 V (criterion A)

Surge susceptibility

EN61000-4-5

  • AC power port: ±6 kV in both horizontal and vertical directions (criterion B)
  • DC power port: ±2 kV in differential mode, ±4 kV in common mode (criterion B)
  • Northbound network port: 1 kV in differential mode, 2 kV in common mode (criterion B); southbound network port: 0.5 kV in differential mode, 1 kV in common mode (criterion B)
  • Dry contact: 1 kV in differential mode, 1 kV in common mode (criterion B)

Surge protection

AC power port: 30 kA in differential mode, 30 kA in common mode (8/20 μs) (criterion C)

AC power port: 20 kA in differential mode, 20 kA in common mode (8/20 μs) (criterion C)